Dual Isolated Half-Duplex RS-485 Repeater
PID: 2541535
Model No: 0
Made in: Taiwan
Quantity:
-
+
1000 Piece(s)Available
Payment:
Send Inquiry
Supplier Details
S
SOYAL TECHNOLOGY CO., LTD.
Member Since
1993
Address
11F., No.368, Gongjian Rd., Xizhi Dist., New Taipei City 22161, Taiwan (R.O.C.)
+886-2-26918039
Contact Seller
View company information >
Product Specifications
Operating Voltage
9~24VDC
rated power
0.4W(9V/46mA:12V34mA:24V15mA)
Communication rate
300-11500bps
Surge Protection
3KV
Responsibility
1-64 nodes
Communication distance
0-1000 meters(theoretical value)
Housing Material
ABS
Dimension (mm)
106.5(H)x66(W)x27.7(D)
Weight(g)
approx. 50
Operation Temperature
-20°C ~ +70°C
Key Features
The two sides of the communication and the power supply adopt triple-layer isolation design , which can provide RS485 clean transmission completely isolated from the system power supply

9-24VDC wide input, Triple-Zone DC/DC power isolation, built-in antisurge, static electricity, and lightning protection.

 The signal isolation strength of automatic direction detection can reach 3.0KV.

Fully transparent data transmission; Support communication protocols such as MODBUS RTU and encrypted transmission.

Industrial-grade RS-485 signal repeater and amplifier distance exten


RS485 wiring precautions

  1. 485 communication lines must use shielded twisted-pair; all 485 equipment on the lines must be connected to same GND ground.

  2. The theoretical length of 485 communication line should not exceed 1000 meters. According to actual experience and on-site environment, it is recommended that the total length should not exceed 500 meters, 485repeater should be added if it exceeds 500 meters.

  3. The theoretical maximum of devices on the 485 bus should not exceed 64; If it exceeds, a 485 repeater should be added.

  4. The 485 bus must be a hand-in-hand bus structure, and resolutely avoid the way of star and bifurcation connection.

  5. The 485 wiring should be as far away from interference sources as possible such as high-voltage power supply / electric mains / high-radio frequency signal cables, and not to be bundled together; if it is necessary to run with these cables in parallel, please add EMT conduit tube.

 
Fullscreen Image
To:
Mr.Sales DepartmentGREAT COMPUTER CORPORATION
Quantity
-
+
Estimated PurchaseAmount
Mamessage
Email
Tel
Submit
This is a notification message!
Restaurants Cafe Plumbing Gym Electrician Dentist Hairdressing Beauty Salon Automotive
Join Poter

To help you see through the fog on Facebook, we generate new features on local directory Poter for social marketing and put together some tips on how to use Facebook for business.

expand_less