Key Features
It can be connected to ventilation system. Wind volume from ventillation can be adjusted according the measurement value to reduce indoor CO2 density. Additonally, it provides the value of indoor temperature and humidity as a reference of comfort and air quality.
Features:
- Continuous monitoring: non-stop detecting and monitoring, complete record, real time update, meet the criteria of " Taiwan indoor air quality act".
- Alarm function: 3 relay output, respectively corresponding to CO2, temperature and humidity. They can activate the HVAC equipment to maintain indoor air quality and save energy.
- Built-in memory: configurations can be stored after power off.
- Meet the criteria of " Taiwan indoor air quality act": record of hourly average value and 8-hour average value
- Data access: with AUS-001 RS485 to USB converter, user can read measurement data from computer
- A calender with year, month, date, day and time.
Specification:
Type: Wall mount
Parameters: CO2, Relative Humidity, Temperature
Operating Environment: -10 ~ 60°C / 0 ~ 95%RH, non-condensing
Storage Temperature: -10 ~ 60°C
Clock: Real time clock with battery backup
Power Supply: 12 VDC (supply with an AC adapter 100 ~ 240V / 50 ~ 60Hz)
Current Consumption: 1.2A (max)
Display: 7 segment LED display
Memory Capacity: 60000 values
CO2 Measurement
Measurement Principle: Non-dispersive infrared (NDIR) with automatic calibration
Measurement Range: 0 ~ 9999 ppm
Accuracy Tolerance: 0 ~ 2000ppm ± 3% and ± 40 ppm (note1 and 2)
Response Time: 2 minutes by 90%
Maintenance: Maintenance-free for normal indoor applications
Environmental: -10 ~ 60°C / 0 ~ 95%RH, non-condensation
Display Digit: 4 digits, 0 ~ 9999
Relay Setting: 1200ppm
Hysteresis: 100ppm
Humidity Measurement
Measurement Range: 0 ~ 95 %RH
Accuracy Tolerance: ± 3 %RH (typical)
Repeatability: ± 0.1 %RH
Response Time τ63: < 8 s (τ63%, 25°C)
Long-term Drift: < 0.5 %RH / year
Display Digit: 2 digits, 0 ~ 99
Relay Setting: 70 %RH
Hysteresis: 5 %RH
Temperature Measurement
Measurement Range: -10 ~ 60°C
Accuracy Tolerance: ± 0.3°C (typical)
Repeatability: ± 0.1°C
Response Time τ63: 5 ~ 30 s (τ63%, 25°C)
Long-term Drift: < 0.04 °C / year
Display Digit: 3 digits (One decimal point), 0.0 ~ 99.9
Relay Setting: 28°C
Hysteresis: 1°C
Outputs
RS-485: RS485 (Modbus RTU)
Relay: 3 Relay outputs for CO2, relative humidity, and temperature respectively. N.O. and N.C. (2A / 30VDC)
Mechanical
Housing Material: PMMA panel (4mm), SPCC casing (1mm)
Dimensions: 527 x 217 x 32 mm
Weight: 2600g