PRODUCT NAME: CIRCUIT BREAKER
SPECIFICATION:
STANDARD RATING: 2-50 AMPERE.
INPUT POWER: 50 VDC /125 VAC / 250 VAC.
DIELECTRIC STRENGTH: 1500 VAC / 1 MINUTE.
INSULATION RESISTANCE : > 100 MΩ.
CALIBRATION:
25-100%OF RATED CURRENT - CONTINUOUSLY CARRIED.
25℃-BETWEEN 101% TO 134% - MAY TRIP OR NOT.
25℃- 135% OF RATED CURRENT - TRIP WITHIN 1 HOUR.
165% OF 3 ~ 4A - TRIP WITHIN 1 HOUR.
25℃- 200% OF RATED CURRENT - TRIP WITHIN 1 MINUTE
CONTACT ENDURANCE:
125VAC x 150% OF RATED CURRENT-500 CYCLES.
DEGREE OF TRIP - FREE BEHAVIOUR: “CYCLING TRIP - FREE “.
RESET: MANUAL PUSH RESET.
APPROVALS: UL,CSA,VDE.
APPLICATION:
AC & DC MOTOR
GENERATOR
POWER STRIP
COMMON PROTECT